Product Detail

Model No.: KCT
Production Capacity: 10000pcs/month
Delivery Date: 7-10 days
Coil Structure: Toroidal
Usage: Current
Primary current: 5-600A
Frequency: 50-2KHz
Phase angle: ≤ ±60min
Insulation Resistance: DC500V/100MΩ min
Bobbin: PBT
Means of Transport: Ocean,Air;global courier
Packing: export carton
Phase: Single
Coil Number: Autotransformer
Brand Name: HEYI
Secondary current: 0.333V(AC)or 0-500mA
Ratio: ≤ ± 1.0%
Dielectric strangth: 2.5KV/1mA/1min
Case: PA/UL94-V0
Core: Silicon steel

split core current transformer KCT is mini cts, calmp on design make easy&safe mounting.

The KCT range of split core current transformers have been specifically designed to be small CT and easy to open and yet maintain the accuracy required for kwh meters. The benefit of a split core current transformer is that it can be placed into position easily and without disturbing or disconnecting the main cables it is monitoring. The KCT range of current transformers has two insulated terminal covers for connecting the S1 and S2 cables which lock down over the terminal screws fully insulating the connections. This makes it ideal to use Autometers cable hamesses which are colour coded and individually numbered on each conductor ensuring simple and easy connection from the current transformer to the electricity meter.


Features:

1:The structure of the self-locking, safe, easy to install, portable

2:Wide inner window, allowing clamping of big cables or bus-bars

3:Wide range of sizes to accommodate all the existing installations

4:Isolated plastic case recognized according to UL94-V0

5:Wires plugs,Audio plugs,Power plugs and so on five kinds of plugs


Applications:

1:Current measurement, monitoring and protection for electrical wiring and equipment.

2:Current and power measurement for electric motors, lighting, air compressor,heating and ventilation system, air-condition equipment and automation – control system.

3:Current, power and energy monitoring device.

4:Relay protection device.


Technique Index:

Electrical Parameter
Mechanical Parameter
Frequency50-2KHzCasePA/UL94-V0
Rated Input5A-200ABobbinPBT
Measuring range10%In-120%InCoreSilicon steel
Rated Output0.333V(AC)or 0-500mAInternal structureEpoxy
Ratio≤ ± 1.0%
ConstructionTie
Phase angle≤ ±60min
Operation Temp-25oC~+75oC
Dielectric strangth2.5KV/1mA/1minOperating Humidity≤85%
Insulation ResistanceDC500V/100MΩ minOutput ConnectionUL1015 20AWG Wire2.5m


Specification:


MODELKCT-6
Current Ratio5A/2.5mA10A/5mA20A/10mA
Primary Current5A10A20A
Max.Current30A30A300A
Output2.5mA5mA10mA
Load Resistance200Ω
100Ω
50Ω
Class0.5/1.0
Turns Ratio2000:12000:12000:1
Protection Level7.5V0-P7.5V0-P
7.5V0-P
Insulation CategoryCATIII
Operating Condition-20℃~+50℃,≤85%RH,No condensation,IN-house&Any direction installable
Storage Condition-30℃~+50℃,≤85%RH,No condensation


MODELKCT-10
Current Ratio5A/2.5mA20A/10mA60A/20mA75A/25mA1~75A/0.333V
Primary Current5A20A60A75A1~75A
Max.Current60A60A750A75A1~75A
Output2.5mA10mA20mA25mA333mV
Load Resistance400Ω
100Ω
50Ω
20Ω
/
Class0.5/1.0
Turns Ratio2000:12000:13000:13000:1/
Protection Level7.5V0-P7.5V0-P7.5V0-P
7.5V0-P
7.5V0-P
Insulation CategoryCATIII
Operating Condition-20℃~+50℃,≤85%RH,No condensation,IN-house&Any direction installable
Storage Condition-30℃~+50℃,≤85%RH,No condensation


MODELKCT-16
Current Ratio100A/33.3mA100A/40mA120A/40mA200A/66.7mA100~200A/0.333V
Primary Current100A100A120A200A100~200A
Max.Current120A120A120A240A240A
Output33.3mA40mA40mA66.7mA333mV
Load Resistance50Ω
/
Class0.5/1.0
Turns Ratio3000:12500:13000:13000:1/
Protection Level7.5V0-P7.5V0-P7.5V0-P
7.5V0-P
7.5V0-P
Insulation CategoryCATIII
Operating Condition-20℃~+50℃,≤85%RH,No condensation,IN-house&Any direction installable
Storage Condition-30℃~+50℃,≤85%RH,No condensation


MODELKCT-24
Current Ratio100A/40mA200A/40mA200A/66.7mA400A/80mA100~400A/0.333V
Primary Current100A200A200A400A100~400A
Max.Current150A240A240A480A4800A
Output40mA40mA66.7mA80mA333mV
Load Resistance50Ω
/
Class0.5/1.0
Turns Ratio2500:15000:13000:15000:1/
Protection Level7.5V0-P7.5V0-P7.5V0-P
7.5V0-P
7.5V0-P
Insulation CategoryCATIII
Operating Condition-20℃~+50℃,≤85%RH,No condensation,IN-house&Any direction installable
Storage Condition-30℃~+50℃,≤85%RH,No condensation


MODELKCT-36
Current Ratio300A/100mA400A/40mA500A/50mA600A/60mA300~600A/0.333V
Primary Current300A400A500A600A300~600A
Max.Current360A480A600A720A720A
Output100mA40mA50mA60mA333mV
Load Resistance50Ω
/
Class0.5/1.0
Turns Ratio3000:110000:110000:110000:1/
Protection Level7.5V0-P7.5V0-P7.5V0-P
7.5V0-P
7.5V0-P
Insulation CategoryCATIII
Operating Condition-20℃~+50℃,≤85%RH,No condensation,IN-house&Any direction installable
Storage Condition-30℃~+50℃,≤85%RH,No condensation


Accuracy class characteristics:


bigPhoto
 Mr. Jake Gao

Tel: 86-577-62659558
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

HEYI Electrical Co., Ltd. [China (Mainland)]


Business Type:Manufacturer, Trading Company
City: Wenzhou
Province/State: Zhejiang
Country/Region: China (Mainland)

You May Like: